SA2100 Power Quality Analyzer Portable Power Quality Analyzer Supplier
Overview
SA2100 Power Quality Analyzer is a handheld multi-functional device which is designed to measure and analyze single or three-phase power system. This portable class S device can provide safe, convenient and accurate measurements for troubleshooting power networks.
Application
Electrical power, medical, transportation, telecommunication, other industrial areas
Design Features
Basic voltage measurement accuracy of±0.5%
1-50th harmonic display
Support dynamic measurement such as Inrush, Flicker and Transients.
10 kinds of language are available to select
Powerful logger function
Specifiations
Measurement Range
|
Resolution
|
Accuracy
|
|
Voltage/Current/Frequency
|
Vrms(AC+DC)
|
1~ 1000Vrms
|
0.1Vrms
|
±0.5% of nominal
voltage
|
Vpk
|
1 ~ 1400Vpk
|
0.1Vpk
|
±0.5% of nominal
voltage
|
V(Crest Factor)
|
1.0 ~>2.8
|
0.01
|
±5%
|
Arms (AC)
|
10mV/A
|
0 ~ 100A
|
0.1A
|
±0.5%±0.2A
|
1mV/A
|
1~1000A
|
0.1A
|
±0.5%±0.2A
|
50mV(65mV)/1000A
|
15~5000A
|
1A
|
±1%±2A
|
A(Crest Factor)
|
1~10
|
0.01
|
±5%
|
Frequency
|
42.5 ~ 57.5Hz
(50Hz nominal)
|
0.01Hz
|
±0.01Hz
|
51 ~ 69Hz
(60Hz nominal)
|
0.01Hz
|
±0.01Hz
|
385~414Hz
(400Hz nominal)
|
0.01Hz
|
±0.1Hz
|
Dips & Swells
|
Vrms1/2
|
0 ~ 200% of
nominal voltage
|
0.1Vrms
|
±1%
|
Arms1/2
|
1 ~ 3000A
|
1A
|
±1%±2A
|
Duration
|
hour-minute-
second-
microsecond
|
0.5 cycle
|
1 cycle
|
Harmonic(IEC61000-4-7)
|
Harmonic Number
|
1 ~ 50
|
Harmonic Voltage %f
|
0.0 ~ 100.0%
|
0.10%
|
±0.1%±nx0.1%
|
Harmonic Current %f
|
0.0 ~ 100.0%
|
0.10%
|
±0.1%±nx0.1%
|
THD
|
0.0 ~ 100.0%
|
0.10%
|
±2.5%
|
Phase
|
-360° ~ 0°
|
1°
|
±nx1.5°
|
Power and Energy
|
Active Power/Apparent Power/Reactive Power
|
1.0 ~ 20.00MW
|
0.1kW
|
±1.5±10 digits
|
KWh
|
0.00kWh ~ 200GWh
|
10Wh
|
±1.5±10 digits
|
Power Factor
|
0 ~ 1
|
0.01
|
±0.03
|
Flicker (IEC61000-4-15)
|
Pst(1min),Pst,Plt,PF5
|
0.00 ~ 20.00
|
0.01
|
±5%
|
Unbalance
|
Voltage
|
0.0 ~ 5.0%
|
0.10%
|
±0.5%
|
Current
|
0.0 ~ 20.0%
|
0.10%
|
±1%
|
Voltage Phase
|
-360° ~ 0°
|
1°
|
±2digits
|
Current Phase
|
-360° ~ 0°
|
1°
|
±5digits
|
Voltage Transient
|
Vpk
|
±6000Vpk
|
1V
|
±15%
|
Vrms
|
10 ~ 1000Vrms
|
1V
|
±2.5%
|
Min. Test Time
|
50us
|
Inrush Current
|
Arms
|
0~3000Arms
|
0.1
|
±1%±5digits
|
Inrush Duration
|
6s ~ 32min
selectable
|
10ms
|
±20ms
|
Logger
|
Recording
|
user-defined parameters for 4 phases at the same time
|
Memory
|
Data stored in Micro SD card, 8GB
|
Duration Time
|
2 hrs to 1 year, depends on the recording items
and time interval
|
Interval
|
1s to 1 hrs
|
Monitor
|
Support EN50160 in default or user-defined standard
|
Channel(Voltage/Current)
|
4/4
|
Voltage Range
|
1-1000Vrms, 6000V transient voltage
|
Current Range
|
depends on supplied current clamp
|
Micro SD card(bulid-in)
|
8GB
|
Battery
|
NI-MH, 3800Ah/>7h
|
interface
|
USB Host, LAN
|
Screen
|
5.6' TFT LCD with resolution320*240(SA2100)
|
Language
|
9-Chinese, English, French, German, Korean, Polish, Portuguese , Spanish, Turkish
|
Dimension/Weight
|
262*173*66mm/1.6kg
|
Wire Combinatios
|
1Ø+NEUTRAL,1Ø SPLIT PHASE,1Ø IT NO NEUTRAL,3Ø
WYE, 3Ø DELTA, 3Ø IT, 3Ø HIGH LEG, 3Ø OPEN LEG,
2-ELEMENT, 2 1/2-ELEMENT
|
Electrical Safety
|
IEC61010-1 ,Safety Degree: 600V CAT IV 1000V CAT III
|
https://www.suindigital.com/power_quality_analyzer/563.html